Product Categories
What's New
Addressable Detection
Conventional Detection
Residential Use Dectectors
About us
Business and Technology
Quality Assurance
OEM/ODM/EMS Services
Manufacturing Services
International Approvals
Contact Us
Sales Inquiry
FAQs
|
Product Categories > Addressable Detection
Addressable Detection
Advanced Multisensing Photoelectric Technology
Intelligent SensorX™ series heat, optical smoke detectors and multisensors
SensorX™ series is state-of-the-art analogue addressable detectors designed to be sensitive to a wide range of fires and may be used in place of an ionisation detector. Efficient, versatile and cost-effective SensorX™ solutions will respond quickly to flaming as well as smoldering fires. Detectors are derived from the finest materials to ensure excellent performance and prevent false alarms.
Operation
The Everday SensorX™ analogue addressable detector can be configured to work as an optical smoke, heat or combined optical smoke / heat detector which is compatible with a version of the Everday protocol used by several fire / security panel manufacturers. It is designed to be sensitive to a wide range of fires and may be used in place of an ionisation detector in many instances.
When polled by the control panel it returns an analogue count determined by responses from optical, heat or both sensors.
Signals from the optical smoke chamber and temperature sensor are independent, and represent the smoke level and air temperature respectively in the vicinity of the detector, the detectors microcontroller processes both signals.
Build-in isolator is optional.
The detector is fitted with a 10-way dipswitch whose function is defined below:
Switch 1 to 8 determines the detectors hardware address 1 to 250.
Switch 9 - Protocol Select
Switch 10 - Hardware/Software Addressing Select
| Terminal 1 = CN5 = ISO-VE | Connection for software addressing only |
| Terminal 2 = CN4 = REM- | Connection for switched remote -VE (RIL) output |
| Output must be limited to 2mA at 24V dc |
| Terminal 3 = CN2 = LP+ | Connection for panel loop +VE and remote +VE (RIL) |
| Terminal 4 = CN3 = LP- | Connection for panel loop -VE |
| Terminal 5 = CN1 = REM+ | Can be used for remote +VE (RIL) limited via 2.2K omhs resistor internally |
Wiring Diagram
Technical Specification
| Operating voltage | 17-28V dc |
| Quiescent current | 400uA |
| Power-up surge | 1mA |
| Alarm current, led on | 4mA |
| Remote output | |
| Connects to neg line | 8mA max |
| Clean air analogue value | 27 +/- 6 |
| Alarm level analogue value | 55 |
| Alarm indicator | 2 Red LEDs, with optional remote LED |
| Amber LED for Optional Isolator | |
| Optional Isolator Indicator | Yellow LED |
| Operating temperature | -20 °C to +70 °C |
| Humidity (no condensation) | 0-95% |
SensorX™ series accessories:
Interested in this product? Send us an Inquiry.
Need more options? Go to Conventional detectors.
|